Leave Your Message
JC3RH-BS Type B RCCB Residual Current Circuit Breaker

RCCB

JC3RH-BS Type B RCCB Residual Current Circuit Breaker

JC3RH-BS Type B RCCBs are suitable for non-linear circuits that are able to generate leakages with high direct current (higher than 6 mA) and/or high frequency components, for example single-phase or poly-phase rectifiers, rectifiers with active correction of the power factor, continuous voltage generator with no separation from AC networks and inverters at variable frequency.

    jc3rh-bi2l

    Features

    ● Electromagnetic Type

    ● Earth leakage protection

    ● Breaking capacity 6kA,10kA

    ● Rated current up to 100A

    ● Detect smooth DC residual currents

    ● Tripping sensitivity: 30mA,100mA,300mA

    ● Connection from top or bottom

    ● Complies with IEC 61008-1 & IEC62423

    Application

    JC3RH-BS Type B RCCBs are suitable for non-linear circuits that are able to generate leakages with high direct current (higher than 6 mA) and/or high frequency components, for example single-phase or poly-phase rectifiers, rectifiers with active correction of the power factor, continuous voltage generator with no separation from AC networks and inverters at variable frequency.

    B Type

    Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.

    29bs

    jc3rh-bl9x


    Standard
    IEC62423 & IEC61008-1
    Electrical
    features
    Type (wave form of the earth leakage sensed)
    B
    Rated current In
    25A, 40A, 63A, 80A, 100A
    Poles
    1P+N, 3P+N
    Rated voltage Ue
    1P+N:230V/240V~; 3P+N:400V/415V~;
    Rated sensitivity I∆n
    0.03A, 0.1A, 0.3A
    Insulation voltage Ui
    500V
    Rated residual making and breaking capacity I∆m
    500 (In=25A/40A), 630 (In=63A), 1000(In=80A/100A
    Short-circuit current Inc=I∆c
    6kA,10kA
    SCPD fuse
    10000A
    break time under I∆n
    ≤0.1 S
    Rated frequency
    50Hz
    Rated impulse withstand voltage(1.2/50) Uimp
    4,000V
    Dielectric test voltage at ind. Freq. for 1 min
    2.5 kV
    Pollution degree
    2
    Mechanical
    features
    Electrical life
    2, 000
    Mechanical life
    10,000
    Fault current indicator
    Yes
    Protection degree
    IP20
    Ambient temperature (with daily average≤35°C)
    -25°C...+40°C
    Storage temperation
    -25°C...+70°C
    Installation
    Terminal connection type
    Cable/U-type busbar/Pin-type busbar
    Terminal size top/bottom for cable
    25/35 mm²
    18-3/18-2 AWG
    Terminal size top/bottom for busbar
    10/16 mm²
    18-8/18-5 AWG
    Tightening torque
    2.5 N·m
    22 In-Ibs.
    Mounting
    On DIN rail EN 60715 (35mm)
    Connection
    From top and bottom
    5zgm

    Leave Your Message