JC3RH-S Residual Current Device
Features
● Electromagnetic Type
● Earth leakage protection
● Breaking capacity 6kA, or 10kA
● Rated current up to 100A
● Available in Type A or Type AC
● Tripping sensitivity: 30mA,100mA,300mA
● Connection from top or bottom
● Complies with IEC 61008-1, EN61008-1
Application
The JC3RH-S RCD (residual current circuit breaker with overload protection) are suitable for consumer units or distribution boards, applied under occasions such as industrial, and commercial, high-rise buildings and residential houses.
Overall, the JCSD1-125 is a must-have accessory for anyone looking to increase the safety and efficiency of their electrical installations. Its intuitive design, rugged construction and compliance with industry standards make it an excellent solution for MCB and RCBO monitoring. With the JCSD1-125, users can control their circuits with confidence knowing they have a reliable and effective tool.
Standard
|
IEC61008-1 , EN61008-1
|
|
Electrical features
|
Rated current In (A)
|
25, 40, 50, 63, 80, 100
|
Type
|
Electromagnetic
|
|
Type (wave form of the earth leakage sensed)
|
AC, A, AC-G, A-G, AC-S and A-S are available
|
|
Poles
|
2 Pole, 4 Pole
|
|
Rated voltage Ue(V)
|
230/240 (2P), 400/415(4P)
|
|
Rated sensitivity I∆n
|
30mA,100mA,300mA are available
|
|
Insulation voltage Ui (V)
|
500
|
|
Rated residual making and breaking capacity I∆m (A)
|
500 (In=25A/40A), 630 (In=63A),
1000(In=80A/100A)
|
|
Rated frequency
|
50/60Hz
|
|
Rated breaking capacity
|
6kA, 10kA
|
|
Rated impulse withstand voltage(1.2/50) Uimp (V)
|
6000
|
|
Dielectric test voltage at ind. Freq. for 1 min
|
2.5kV
|
|
Pollution degree
|
2
|
|
Mechanical features
|
Electrical life
|
2, 000
|
Mechanical life
|
2, 000
|
|
Contact position indicator
|
Yes
|
|
Protection degree
|
IP20
|
|
Reference temperature for setting of thermal
element(°C)
|
30
|
|
Ambient temperature (with daily average ≤35°C)
|
-5...+40
|
|
Storage temperature (°C)
|
-25...+70
|
|
Installation
|
Terminal connection type
|
Cable/U-type busbar/Pin-type busbar
|
Terminal size top/bottom for cable
|
25mm2 , 18-3/18-2 AWG
|
|
Terminal size top/bottom for Busbar
|
10/16mm2 ,18-8 /18-5AWG
|
|
Tightening torque
|
2.5 N*m / 22 In-Ibs.
|
|
Mounting
|
On DIN rail EN 60715 (35mm)
|
|
Connection
|
From top or bottom
|