JCB3-80M Miniature Circuit Breaker 6kA

MCB

JCB3-80M Miniature Circuit Breaker 6kA

JCB3-80M Miniature Circuit Breakers for use in domestic installations, as well as commercial and industrial distribution systems.

Short circuit and overload protection
6kA breaking capacity
With contact indicator
Can be made from 1A to 80A
1 Pole, 2 Pole, 3 Pole , 4 Pole are available
B , C or D curve
Comply with IEC 60898-1

    Introduction

    JCB3-80M Miniature circuit breaker is designed to protect installations from overloads and short circuits, ensuring reliability and safety under all operating conditions.They all comply with IEC 60898-1 and EN 60898-1 standard. This range of MCBs offer solutions for many different applications, either for domestic, small commercial or industrial solutions. Our JCB3-80M circuit breakers ensure electrical safety in homes, offices and other buildings as well as for industrial applications by protecting electrical installations against overloads and short circuits.

    JCB3-80M MCBs have a short circuit breaking capacity of 6kA. They are din rail mounted. They all can be made with B, C, D curve. B curves trips off the circuit when the current exceeds 3-5 times the actual current flow and finds its application in the cable protection. C Curve trips off the circuit when the current exceeds 5-10 times the actual current flow and finds its application in the domestic as well as commercial appliances like transformers, fluorescent lighting circuits, IT equipment like personal computers, servers, and printers. D curves trips off the circuit when the current exceeds 10-20 times the actual current flow and offers high resistance. It finds its application in motors.

    JCB3-80M MCBs have a positive indication for On or Off and the operating switch may be locked in either position without affecting operation of the trip mechanism.When in the off position the contact gap is 4 mm meaning that the MCB may be used as single pole isolating switch where appropriate.

    Housing of JCB3-80M is made of flame-retardant, environmentally friendly, and safe materials. Flame retardant grade up to V1.

    JCB3-80M MCBs automatically switch off the electrical circuit during the abnormal conditions of the network and faulty conditions to prevent damage. The defective zone of the electric circuit can easily be detected as its switch operating knob is in the off place during tripping of short circuits. In the case of Miniature Circuit Breakers, quick restoration is possible by just switching an operation.

    JCB3-80M MCBs is perfect for use in domestic circuit protection, they detect overcurrents due to both overload and fault and will operate to interrupt the electrical supply thus preventing damage to the installation and devices

    Product Description

    1-34cg6

    The JCB3-80M circuit breaker offers a comprehensive range of features and functions, making it an indispensable component in electrical installations. With a breaking capacity of up to 6kA, these circuit breakers provide strong short-circuit and overload current protection, ensuring the safety and reliability of electrical systems. Contains contact indicators, green for "off" and red for "on", for enhanced visibility and easy monitoring.

    The JCB3-80M circuit breaker has a high nominal current range of up to 80A, making it suitable for a wide range of applications. Their availability in 1-, 2-, 3- and 4-pole configurations and B, C or D curves provides flexibility and customization to meet specific requirements. Additionally, its 35mm Din rail mounting ensures optimal ease of installation and connection, further enhancing its practicality and efficiency.

    Functionally, these circuit breakers serve a variety of purposes, including protecting circuits from short circuits and overload currents, acting as switches, and providing isolation when necessary. Their versatility and reliability make them ideal for use in home installations as well as commercial and industrial power distribution systems.

    When selecting a suitable JCB3-80M circuit breaker, it is crucial to consider the technical data of the installation point network. This includes evaluating the short-circuit current at the grounding system (TNS, TNC), at the point where the circuit breaker is installed, and ensuring that it is always less than the breaking capacity of the equipment and the normal voltage of the network.

    These circuit breakers provide tripping curves that provide tailored protection for each situation.  Curve B provides protection for personnel and long cables in TN and IT systems, Curve C provides protection for resistive and inductive loads with low inrush currents, Curve D provides protection for circuits supplying loads at high inrush currents at low voltage / The closing of circuits such as low-voltage transformers and fault lights demonstrates the adaptability and precision of JCB3-80M circuit breakers in meeting different application requirements.

    2-328zp

    Technical Data

    ● Standard: IEC 60898-1, EN 60898-1

    ● Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A,80A

    ● Rated working voltage: 110V, 230V ~ (1P, 1P + N), 400V ~ (2 ~ 4P, 3P + N)

    ● Rated breaking capacity: 6kA

    ● Insulation voltage: 500V

    ● Rated impulse withstand voltage(1.2/50) : 4kV

    ● Thermo- magnetic release characteristic: B curve, C curve, D curve

    ● Mechanical life: 20,000 times

    ● Electrical life: 4000 times

    ● Protection degree: IP20

    ● Ambient temperature (with daily average ≤35℃):-5℃~+40℃

    ● Contact position indicator: Green=OFF, Red=ON

    ● Terminal connection type:Cable/U-type busbar/Pin-type busbar

    ● Mounting: On DIN rail EN 60715 ( 35mm) by means of fast clip device

    ● Recommended torque: 2.5N.m

    ● Combination with accessories: Auxiliary contact,Shunt release,Under voltage release, Alarm contact

      Standard IEC/ EN 60898- 1  IEC/ EN 60947- 2
    Electrical features Rated current In ( A) 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63, 80
    Poles 1P, 1P+ N, 2P, 3P, 3P+ N, 4P 1P, 2P, 3P, 4P
    Rated voltage Ue( V) 230/ 400~ 240/ 415
    Insulation voltage Ui ( V) 500
    Rated frequency 50/ 60Hz
    Rated breaking capacity 6kA
    Energy  limiting class 3  
    Rated impulse withstand voltage( 1. 2/ 50) Uimp ( V) 4000
    Dielectric test voltage at ind. Freq. for 1 min ( kV) 2
    Pollution degree 2
    Power  loss  per pole Rated  current  ( A)
    1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63, 80
    Thermo- magnetic release characteristic B, C, D 8- 12In, 9. 6- 14. 4In
    Mechanicalfe atures Electrical life 4,000
    Mechanical life 20,000
    Contact position indicator Yes
    Protection degree IP 20
    Reference temperature for setting of thermal element(℃) 30
    Ambient temperature ( with daily average ≤35℃) - 5...+40 ℃
    Storage temperation (℃) -25...+ 70 ℃
    Installation Terminal connection type Cable/ U- type busbar/ Pin- type busbar
    Terminal size top/ bottom for cable 25mm2 / 18- 4 AWG
    Terminal size top/ bottom for busbar 10mm2 / 18- 8 AWG
    Tightening torque 2. 5 N* m / 22 In- Ibs.
    Mounting On DIN rail EN 60715 ( 35mm) by means of fast clip device
    Connection From  top  and bottom
    Combination withaccessori es Auxiliary contact Yes
    Shunt release Yes
    Under voltage release Yes
    Alarm contact Yes
    6KA-MCBnv1Dimensionskmr