JCR1-40 Single Module Mini RCBO with Switched Live and Neutral 6kA
Introduction
JCR1-40 RCBO provides protection against earth faults, overloads, short circuits and domestic installation. The RCBO with both disconnected neutral and phase guarantees its proper actuation against earth leakage faults even when the neutral and phase are wrongly connected.
JCR1-40 electronic RCBO incorporates a filtering device preventing the risks of unwanted due to transient voltages and transient currents;
JCR1-40 RCBO's combine the overcurrent functions of an MCB with the earth fault functions of an RCD in a single unit.
JCR1-40 RCBO, which does the job of both an RCD and MCB, thus prevents this type of nuisance tripping and should be used on mission critical circuits.
JCR1-40 miniature RCBO's provide more wiring space in the enclosure for the installer making the whole installation process easier and quicker. During installation, resistance testing live and neutral conductors do not have to be disconnected. Now with an increased level of safety these JCR1-40 RCBO’s include switched neutral as standard. A faulty or damaged circuit is fully isolated by disconnecting the live and neutral conductors. Healthy circuits remain in service, only the faulty circuit is switched off. This avoids danger and prevents inconvenience in the event of a fault.
Type AC RCBOs are used for general purpose on AC (Alternating Current) only circuits. Type A are used for DC (Direct Current) protection, these mini RCBOs provide both levels of protection.
The A Type JCR1-40 RCBO responds to both AC and pulsating DC residual currents. It protects against both overcurrents due to overload and fault and residual current earth leakage. In either event, the RCBO interrupts the electrical supply to the circuit thus preventing damage to the installation and devices and electric shock to humans.
B curve JCR1-40 RCBO trips between 3-5 times full load current is suited for domestic application. C curve JCR1-40 rcbo trips between 5-10 times full load current is suited for commercial applications where there is greater chance of higher short circuit currents, such as inductive loads or fluorescent lighting.
JCR1-40 Available in current ratings that range from 6A to 40A and in B and C type tripping curves.
JCR1-40 RCBO Complies with BS EN 61009-1, IEC 61009-1, EN 61009-1, AS/NZS 61009.1
Product Description
Standard |
IEC/EN 61009-1 |
|
Electrical features |
Rated current In (A) |
6, 10, 16, 20, 25, 32, 40 |
Type |
Electronic |
|
Type (wave form of the earth leakage sensed) |
A or AC are available |
|
Poles |
1P+N( Switched Live and Neutral) |
|
Rated voltage Ue(V) |
230/240 |
|
Rated sensitivity I△n |
30mA, 100mA,300mA |
|
Insulation voltage Ui (V) |
500 |
|
Rated frequency |
50/60Hz |
|
Rated breaking capacity |
6kA |
|
Rated residual making and breaking capacity I△m (A) |
3000 |
|
Rated impulse withstand voltage(1.2/50) Uimp (V) |
4000 |
|
Break time under I△n (s) |
≤0.1 |
|
Pollution degree |
2 |
|
Thermo-magnetic release characteristic |
B, C |
|
Mechanical features |
Electrical life |
2, 000 |
Mechanical life |
2, 000 |
|
Contact position indicator |
Yes |
|
Protection degree |
IP20 |
|
Reference temperature for setting of thermal element(℃) |
30 |
|
Ambient temperature (with daily average ≤35℃) |
-5...+40 |
|
Storage temperation (℃) |
-25...+70 |
|
Installation |
Terminal connection type |
Cable/Pin-type busbar |
Terminal size top for cable |
10mm2 |
|
Terminal size bottom for cable |
16mm2 / 18-8 AWG |
|
Terminal size bottom for busbar |
10mm2 / 18-8 AWG |
|
Tightening torque |
2.5 N*m / 22 In-Ibs. |
|
Mounting |
On DIN rail EN 60715 (35mm) by means of fast clip device |
|
Connection |
From bottom |