WLM7HU-630-3300 3P Photovoltaic solar type molded case circuit breaker solar mccb 800VAC/1000VAC/1140VAC 630A 3 Poles
MCCB Highlights
1. Advanced and safe arc extinguishing system structure design;
2. Zero flashover can be achieved by installing the protective cover. Double insulation: pole to pole connection and complete isolation of main circuit;
The products are widely used in the field of new energy. AC MCCB: series inverter application (power station type): PV string is inverted by inverter DC/AC, and the output AC is boosted and connected to the grid after being converged by AC combiner box. AC combiner box and low-voltage side of box substation shall be equipped with AC circuit breaker, with working voltage of AC900V → AC1140V. The operating voltage of direct grid connection mode is relatively low, generally less than AC400V.
Main performance index of WLM7HU series circuit breaker
WLM7HU Moulded Case Circuit Breaker |
630 | ||||||||||||
Rated operating current In (A),40℃ |
400-500-630 | ||||||||||||
Rated insulation voltage Ui (V) | 1250 | ||||||||||||
Rated impulse withstand voltage (kV) | 12 | ||||||||||||
Rated operational voltage Ue(V),AC 50/60Hz | 415/690/800/1000/1140v
|
||||||||||||
Breaking capacity code | - | M | H | ||||||||||
Number of poles |
3P |
- | ■ | ■ | |||||||||
AC415V | - | - | 100 | ||||||||||
AC690V | - | 60 | 65 | ||||||||||
Rated ultimate
short-circuit breaking
capacity Icu(kA)
|
AC800V | - | 50 | 50 | |||||||||
AC1000V | - | 20 | 30 | ||||||||||
AC1140V | - | 15 | 20 | ||||||||||
AC415V | - | - | 100 | ||||||||||
AC690V | - | 60 | 65 | ||||||||||
Rated service breaking
capacity Ics(kA)
|
AC800V | - | 37.5 | 50 | |||||||||
AC1000V | - | 20 | 30 | ||||||||||
AC1140V | - | 15 | 20 | ||||||||||
Standard | |||||||||||||
Utilization category | |||||||||||||
Ambient temperature | |||||||||||||
Safety of insulation | |||||||||||||
Arcing distance | |||||||||||||
Mechanical life
(CO recycle)
|
Maintenance free | 15000 | |||||||||||
Electrical life
(CO recycle)
|
Maintenance free | 1000-5000 | |||||||||||
Release units | |||||||||||||
Distribution protection |
TM | ■ | |||||||||||
Mounting and connection | |||||||||||||
Fixed |
Front connection | ■ | |||||||||||
Rear connection | ■ | ||||||||||||
Plug-in |
Front connection | ■ | |||||||||||
Rear connection | ■ | ||||||||||||
Draw-out | Front connection | - | |||||||||||
Rear connection | - | ||||||||||||
DIN rail |
Front connection | - | |||||||||||
Dimension | |||||||||||||
Dimension (mm)
W×H×D
|
Width | 182 | |||||||||||
Height | 270 | ||||||||||||
Depth | 125.8 | ||||||||||||
Weight | |||||||||||||
Weight(kg)/Fixed |
3P | 8 |
Overall and installation dimensions of circuit breaker