JCB1-125 Miniature Circuit Breaker 6kA/10kA
Introduction
JCB1-125 circuit breaker is designed to offer a high industrial performance level, it protects circuit against short circuit and overload current. 6kA/10kA breaking capacity makes it the perfect choice in commercial and heavy industrial applications.
JCB1-125 circuit breaker have been made from the highest grade components. This is to ensure reliability in all applications where protection against overload and short circuit is required.
JCB1-125 circuit breaker is a low voltage multistandard miniature circuit breaker (MCB), the rate current up to 125A. The frequency is 50Hz or 60Hz. The presence of green strip guarantees contact open physically and allows work to be carried out safely on the downstream circuit. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C
JCB1-125 circuit breaker has good overvoltage withstand capacity. It has an electrical endurance going up to 5000 cycles and a mechanical endurance going up to 20000 cycles.
JCB1-125 circuit breaker complete with 27mm pole width and ON/OFF indicators. it can be clipped on a 35mm DIN rail. It has a pin type busbar terminal connection
JCB1-125 circuit breaker comply with both industrial standard IEC 60898-1, EN60898-1, AS/NZS 60898 and residential standard IEC60947-2, EN60947-2, AS/NZS 60947-2
JCB1-125 circuit breaker is available in various breaking capacities, these breakers are the perfect choice for a wide variety of applications.
Product Description
Technical Data
Standard | IEC/EN 60898-1 | IEC/EN 60947-2 | |
Electrical features |
Rated current In (A) | 1, 2, 3, 4, 6, 10, 16, | |
20, 25, 32, 40, 50, 63,80 | |||
Poles | 1P, 1P+N, 2P, 3P, 3P+N, 4P | 1P, 2P, 3P, 4P | |
Rated voltage Ue(V) | 230/400~240/415 | ||
Insulation voltage Ui (V) | 500 | ||
Rated frequency | 50/60Hz | ||
Rated breaking capacity | 10 kA | ||
Energy limiting class | 3 | ||
Rated impulse withstand voltage(1.2/50) Uimp (V) | 4000 | ||
Dielectric test voltage at ind. Freq. for 1 min (kV) | 2 | ||
Pollution degree | 2 | ||
Power loss per pole | Rated current (A) | ||
1, 2, 3, 4, 5, 6, 10,13, 16, 20, 25, 32,40, 50, 63, 80 | |||
Thermo-magnetic release characteristic | B, C, D | 8-12In, 9.6-14.4In | |
Mechanical features |
Electrical life | 4, 000 | |
Mechanical life | 20, 000 | ||
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Reference temperature for setting of thermal element(℃) | 30 | ||
Ambient temperature (with daily average ≤35℃) | -5...+40 | ||
Storage temperation (℃) | -35...+70 | ||
Installation | Terminal connection type | Cable/U-type busbar/Pin-type busbar | |
Terminal size top/bottom for cable | 25mm2 / 18-4 AWG | ||
Terminal size top/bottom for Busbar | 10mm2 / 18-8 AWG | ||
Tightening torque | 2.5 N*m / 22 In-Ibs. | ||
Mounting | On DIN rail EN 60715 (35mm) by means of fast clip device | ||
Connection | From top and bottom | ||
Combination |
Auxiliary contact | Yes | |
Shunt release | Yes | ||
Under voltage release | Yes | ||
Alarm contact | Yes |