JCB2LE-80M4P 4 Pole RCBO 6kA Residual Current Circuit Breaker
Introduction
JCB2LE-80M4P RCBO combines RCD and MCB protection in a 4 module wide device and is operating for unbalanced loads and balanced loads, 3 phase protection in DIN rail distribution box.
JCB2LE-80M4P RCBO (Residual Current Circuit Breaker with Overload Protection) provides residual and overload protection in one neat device. The breaking capacity is up to 6kA. The rate current is up to 80Amps. It is available in 6A, 10A, 16A, 20A, 32A, 40A, 50A, 63A,80A. It is available in A type and AC type. Type AC RCBOs are used for general purpose on AC (Alternating Current) only circuits. Type A are used for DC (Direct Current) protection. Available in 30mA,100mA,300mA tripping sensitivity. Available in B, C ,D tripping curves.
JCB2LE-80M4P RCBO is commonly used in applications where there is the need to combine protection against overcurrents (overload and short-circuit) and protection against earth leakage currents. They help in sensing this kind of faults and trip the circuit ensuring complete protection of the people and connected equipment
JCB2LE-80M4P RCBO is purposed to protect one from the risk of electrical shocks, firesand electrocution. It can also assist in sudden earth faults. The installation of an JCB2LE-80M4P RCBO ensures that a circuit trips immediately and protects you from electric shock.
JCB2L3-80M4P comply with IEC 61009-1, EN61009-1 standard.
Product Description
Standard |
IEC61009-1 , EN61009-1 |
|
Electrical features |
Rated current In (A) |
6, 10, 16, 20, 25, 32, 40,50,63,80 |
Type |
Eletronic |
|
Type (wave form of the earth leakage sensed) |
A or AC are available |
|
Poles |
4 Pole |
|
Rated voltage Ue(V) |
230/240 |
|
Rated sensitivity I△n |
30mA,100mA,300mA |
|
Insulation voltage Ui (V) |
500 |
|
Rated frequency |
50/60Hz |
|
Rated breaking capacity |
6kA |
|
Rated impulse withstand voltage(1.2/50) Uimp (V) |
6000 |
|
Pollution degree |
2 |
|
Thermo-magnetic release characteristic |
B, C |
|
Mechanical features |
Electrical life |
2, 000 |
Mechanical life |
10, 000 |
|
Contact position indicator |
Yes |
|
Protection degree |
IP20 |
|
Reference temperature for setting of thermal element(℃) |
30 |
|
Ambient temperature (with daily average ≤35℃) |
-5...+40 |
|
Storage temperation (℃) |
-25...+70 |
|
Installation |
Terminal connection type |
Cable/U-type busbar/Pin-type busbar |
Terminal size top/bottom for cable |
25mm2 / 18-4 AWG |
|
Terminal size top/bottom for Busbar |
10mm2 / 18-8 AWG |
|
Tightening torque |
2.5 N*m / 22 In-Ibs. |
|
Mounting |
On DIN rail EN 60715 (35mm) by means of fast clip device |
|
Connection |
From top |