JCB1LE-125 125A RCBO 6kA
Introduction
The JCB1LE-125 RCBOs (residual current circuit breaker with overload protection) are suitable for distribution boards, applied under occasions such as industrial, and commercial, high-rise buildings and residential houses.
They are suitable for AC 50Hz, single phase, 3 phase, rated current from 63A to 125A circuit.
They prevent earth leakage, direct or indirect contact electric shock and other faults, and are applicable to low-voltage terminal power distribution in such fields as industry, civil construction, energy, communication and infrastructure. They provide short-circuit protection, overload protection, leakage protection and isolation protection.
When personal electric shock or grid leakage, When the current exceeds the specified value, JCB1LE-125 RCBO will be quickly cut off the faulty power supply in a very short time to protect the safety of people and electrical equipment. At the same time, it can protect the line from overload or short-circuit, and it can also be used as an infrequent conversion of the line.
Combination of ELCB & MCB (EL+MCB) offers 3 in 1 protection against -overload, short circuit and earth leakage
Product Description
Standard |
IEC61009-1 , EN61009-1 |
|
Electrical features |
Rated current In (A) |
63,80,100,125 |
Type |
Electronic |
|
Type (wave form of the earth leakage sensed) |
A or AC are available |
|
Poles |
1 pole, 2 Pole, 3 pole, 4 pole |
|
Rated voltage Ue(V) |
230/240 |
|
Rated sensitivity I△n |
30mA,100mA,300mA |
|
Insulation voltage Ui (V) |
500 |
|
Rated frequency |
50/60Hz |
|
Rated breaking capacity |
6kA |
|
Rated impulse withstand voltage(1.2/50) Uimp (V) |
6000 |
|
Pollution degree |
2 |
|
Thermo-magnetic release characteristic |
B, C |
|
Mechanical features |
Electrical life |
2, 000 |
Mechanical life |
2, 000 |
|
Contact position indicator |
Yes |
|
Protection degree |
IP20 |
|
Reference temperature for setting of thermal element(℃) |
30 |
|
Ambient temperature (with daily average ≤35℃) |
-5...+40 |
|
Storage temperation (℃) |
-25...+70 |
|
Installation |
Terminal connection type |
Cable/Pin-type busbar |
Terminal size top/bottom for cable |
16~50/6-1/0 AWG |
|
Terminal size top/bottom for Busbar |
16~35mm2 / 6-2 AWG |
|
Tightening torque |
3.5 N*m / 31 In-Ibs. |
|
Mounting |
On DIN rail EN 60715 (35mm) by means of fast clip device |
|
Connection |
From top or bottom are available |
JCB1LE-125 Dimensions